A versioned, Telure-curated program of checks for a building core, written in Telure’s own words and organized by how the facility actually runs: the daily rhythm first, then the recurring program above it. It is a documented reference the facility measures its own work against and records reasons against, not a certification. The basis register below shows what informs it, and at what depth.
Alignment tracker
Inside Telure, this list is an alignment tracker a facility turns on with a checkbox. The recurring program below is its clause list, informed by the manufacturer's manual and general safety practice, because no consensus operational standard exists for this facility type. The facility matches its own tasks, checklist items and training items to the clauses they cover, marks the clauses that do not apply with a written reason, and its exports state what share of the rest has a check behind it.
This tracker is Telure's own clause list, informed by the organization's published document. It does not replace reading that document yourself and verifying your facility against it, and marking a clause here is a note on your own record, not a statement by that organization. Where equipment is involved, the manufacturer's documentation governs.
The daily rhythm
Opening walk
Walked before the doors open, item by item, each answer attributed to the person who gave it. The starting set for a building core:
- Exit doors open from the inside without a key or a tool
- Exit doors and the corridors and stairs leading to them clear and unobstructed
- Nothing propped, chained, wedged or blocked at any exit door
- Exit signs lit and readable from the direction of travel
- Stair treads, nosings and handrails sound; stairwells clear of storage
- Extinguishers in their brackets, visible, and unobstructed from the corridor
- AED cabinet unlocked or unobstructed with the status indicator showing ready
- First aid kit at the front desk stocked and closed
- Fire alarm panel showing normal: no trouble, supervisory or alarm condition
- Pull stations, horns and strobes unobstructed and nothing hung from them
- Storage kept down off the ceiling, with nothing stacked against a sprinkler head, a detector or a light fitting
- Chemical storage closed and locked with nothing left out on the floor
- Electrical panels and mechanical room doors closed with clear access to them
- Assembly point route clear and the evacuation maps still on the wall where they belong
During hours
Anything flagged during the day opens a corrective entry on the spot: the item, the finding, and who saw it. Taking equipment or an area out of service is a recorded event with a name attached, and so is returning it. Nothing waits for the end of the shift to become a record.
Closing check
The end-of-day counterpart every facility runs: securing the space and making sure nothing the day surfaced dies overnight.
- Activity areas clear: no members left inside
- Hazards cleared from floors and landing surfaces
- Equipment secured, stowed, or powered down per procedure
- Today's flagged items have maintenance entries opened
- First aid and rescue equipment restocked if used today
- Exits clear; doors, gates and access points secured
The recurring program
The work above the daily walk. Each task surfaces on the day it is due and escalates as it goes overdue. Where a check addresses a published designation, the citation chip names it; a chip is a reference, never a compliance claim.
Weekly
Exit door, egress route and stairway walk
Walk every exit and the route to it, and open each exit door from the inside the way somebody leaving in a hurry would. Record what it actually took to get it open and flag anything that needed a key, a tool, or a second latch to work out in the dark; where your jurisdiction or your insurer sets what that hardware has to do, that governs and the flag is judged against it. Then the route itself, which is what actually changes week to week: nothing propped, chained, wedged or stacked at a door, corridors and stair landings clear of storage and deliveries, stair treads, nosings and handrails sound, and the discharge outside clear of vehicles, bins and snow. This is weekly and not monthly because an exit is blocked by ordinary use rather than by wear: a pallet gets left, a table gets moved, a mat gets rolled up against a door, and none of it survives a month unnoticed but all of it survives a week. Where your jurisdiction or your insurer sets the interval, that governs. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
Monthly
Portable fire extinguisher check: unit by unit
Unit by unit against the registry, not a count of what you happened to see. At each one: present and in its bracket or cabinet at the location it is registered to, visible and unobstructed from the corridor, the gauge needle in the operable band, the pull pin seated and the tamper seal unbroken, the hose and nozzle clear and uncracked, the shell free of dents, corrosion and paint over the label, the instruction label legible and facing out, and the unit not obviously light in the hand. Record the finding against that specific unit and read its hydrostatic and service dates back against the registry while you are there. Monthly because every one of those is a state that changes on the scale of weeks: a seal walks off, a gauge drifts down, a unit gets carried to a workshop and never comes back, and a stack of chairs appears in front of a cabinet. Anything failed comes off the wall, gets replaced from the spares, and opens a corrective item. Where your jurisdiction or your insurer sets the interval, that governs. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
AED readiness check: pads, battery and cabinet access
Every AED in the building and anything the association keeps in a vehicle: the status indicator showing ready rather than any error or blank, the case undamaged and the unit sitting where it is registered, the cabinet unlocked or openable without a key and unobstructed by anything that has been stacked in front of it, and the spare pads, shears and razor in the pouch. Then read the printed expiry date off the pad pouch and the install-by or expiry date off the battery and record both, so the dates live on this record rather than on a sticker somebody has to remember to look at, and the next review opens with them already in front of it. Monthly because a pad pouch reaches its date silently and a cabinet gets blocked by a table within days. Replacement schedules and the self-test the unit runs on its own come from the manufacturer's documentation. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
Emergency light and exit sign function test
Unit by unit, press the test button or drop the local supply and hold it long enough to watch what happens: both lamp heads striking and staying lit, the head aimed where it was aimed, the sign face lit and readable from the direction of travel, and no unit dropping out early or flickering as it warms. Then walk the route with the units on and answer the question the individual test cannot: is the path from here to the exit actually lit, or is there a dark stretch at a turn, on a landing, or where a wall got built since the units went in. A short function test at a monthly interval is what tells you a lamp or a transfer circuit has failed; a battery that has lost its capacity shows up only on the full-duration test below. Where your jurisdiction or your insurer sets the interval or the duration, that governs. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
Fire alarm panel and device walk
Start at the panel and read it: normal, or a trouble, supervisory or alarm condition, and if there is one, what it says word for word and how long it has been there. Note any zone or device that has been isolated or disabled, who isolated it, and whether it is still meant to be. Then walk the building and look at the devices: pull stations unobstructed and their covers intact, smoke and heat detectors clear of paint, tape, plastic, dust and anything hung from them, nothing stacked into the space below a detector, horns and strobes unobstructed with a clear line of sight. Monthly because these fail by housekeeping rather than by wear: a paint crew bags a detector and does not come back for it, a storage rack goes up under one, a poster goes over a pull station. Testing and the intervals for it belong to your alarm service provider and to the code your jurisdiction has adopted; this is the walk in between. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
First aid kit inventory and restock
Open every kit and station in the building, at the front desk, in the program wing, in the kitchen and in any vehicle, and inventory it against its own contents list rather than by eye: quantities of each item present, nothing expired, sterile packaging unopened and undamaged, and the kit itself closed, clean and where it is registered. Restock what is short the same day and record what you replaced, because the pattern of what runs out is itself worth having when somebody asks what injuries this building actually sees. Monthly because a kit is depleted by use and use is invisible: nobody reports taking the last two gauze pads. Which contents list you inventory against is your own choice and your carrier's, and the list you adopt is what you record here. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
Chemical storage and safety data sheet check
Every place chemicals are kept, which in most buildings means the custodial closet, the mechanical room, the kitchen and the maintenance shop: containers closed, upright, labeled with what is actually in them, and segregated so nothing incompatible shares a shelf; no decanted product in an unlabeled bottle; secondary containment intact and dry; ventilation running; the spill kit complete; and nothing stored on the floor or above shoulder height. Then the paperwork half, at the place it is actually kept: a safety data sheet present and findable for every product on the shelf, including the ones somebody bought at a hardware store and brought in, and the staff who work in there able to say where the sheets are. Finish by flushing the eyewash and drench shower where there is one and dating the flush. Monthly because the shelf changes constantly and the sheets do not follow the purchase. Confirm the PPE staff are expected to wear is stocked and serviceable. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
addressing 29 CFR Part 1910Electrically locked and delayed egress door release check
For every exit door with an electric lock, a magnetic hold-open, a delayed egress device or a card reader on it: operate the release the way somebody leaving in a hurry would, and watch the door actually release. Then take the power off it and watch it release again, because a door that unlocks on a button and not on a power failure is a door that works only on the days nothing is wrong. Confirm any delay runs the interval it is set to and no longer, that the local alarm sounds, that the sign on the door still matches what the hardware does, and that a magnetic hold-open drops when the alarm is put into test. Monthly because access control gets reprogrammed by people who are thinking about security rather than about egress, and a change made on a Tuesday afternoon is invisible until somebody needs the door. A building with no electrified egress hardware anywhere has nothing to test here and should mark this as not applicable with the reason recorded. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
Quarterly
Evacuation and lockdown drill
Run one drill and rotate the scenario each quarter: a full evacuation to the assembly point, a lockdown, a shelter in place, and an evacuation with the primary route blocked so the second one gets used. Record the date and time, the scenario, who ran it, how the notification was started, how long the building took to clear or secure, the count at the assembly point against who was signed in, and every single thing that went wrong, including the ones that are embarrassing: the door nobody could find the key for, the wing that did not hear the horns, the group that walked back in before they were told to. The failures are the reason to run it, so a drill recorded as flawless is a drill recorded badly. Quarterly is the cadence this pack proposes; where your jurisdiction, your school district or your licensing body sets a frequency or a scenario, that governs and you record the drills you actually owe. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
Every 6 months
Evacuation map, assembly point and emergency contact check
Stand at each posted evacuation map and read it as a stranger would: is it still on the wall, is it legible, does the you-are-here mark match where you are standing, and does the route it shows still exist after whatever walls, doors and rooms have changed since it was printed. Then the assembly point itself: reachable on the route shown, clear of vehicles and deliveries, far enough from the building, and workable in winter. Finish at the emergency contact list wherever it is posted and confirm every name and number on it is still a person who works here and still a number that answers. Twice a year because all three drift with staff turnover and building work rather than with wear, and both of those move on a scale of months. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
Yearly
Emergency light and exit sign duration test
Once a year, put the emergency lighting on battery and leave it there for its full rated duration rather than for the few seconds the monthly test uses, then walk the egress routes at the end of that period and record what is still lit and what is not. This is the only test that finds the failure that matters: a battery that lights the head for thirty seconds and is flat well before anyone has finished getting out. Record the duration you ran, the units that dropped early and how early, and open a corrective item for each one. Run it when the building is empty, tell your alarm monitoring provider first, and where your jurisdiction, your insurer or the unit's manufacturer sets the duration or the interval, that governs. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
Service tag check: extinguishers, alarm panel and emergency lighting
In the days after each annual service visit, walk the building and look at the tags themselves: on each extinguisher, a tag or collar present, attached, legible and carrying this year's service date and the name or license of whoever performed it; at the alarm panel, the inspection and testing record card filled in and left where it belongs without covering the display or the wiring diagram; on the emergency lighting, whatever record the service provider leaves. This is a physical fixture you look at and answer pass or flag, not a piece of paperwork, and it sits here rather than on a monthly walk because a tag is only ever correct immediately after the visit. Copy what each tag says onto the registered unit as well, so the unit's history survives a tag that fades, gets painted over or leaves with the unit. File the service report against this task and open a corrective item for every deficiency it cites, naming who owns it and when it is due in the item note. Telure records the visit; it does not issue, verify or endorse anybody's license or qualification. Part of the Telure Standard: the manufacturer's manual governs all equipment intervals.
The basis register
What informs this pack, at what reference depth, and when each entry was last checked against its source. An entry here means the pack is informed by the document named; it never means the pack, or any facility using it, is certified to or compliant with it.
| Source | Tier | Jurisdiction | Access | Verified |
|---|---|---|---|---|
| 29 CFR Part 1910US Occupational Safety and Health AdministrationOSHA general industry regulations for employee safety. OSHA has stated that general-industry standards govern employees at amusement and water facilities, while patron safety is regulated at the state level. Public domain. | Tier 1Public law | US | Free to read | Checked 2026-08-31 |
| OSH Act General Duty Clause, section 5(a)(1) (29 U.S.C. 654(a)(1))US Congress / US Department of LaborEmployers must keep the workplace free of recognized hazards likely to cause death or serious physical harm to employees. Public domain. | Tier 1Public law | US | Free to read | Checked 2026-08-31 |
| Manufacturer documentation for installed equipmentOperator-supplied manuals, bulletins and service documents. Where any pack cadence differs from a manufacturer's documented interval, the manufacturer's interval governs. | Tier 5Manufacturer documentation | n/a | Operator-supplied | Not independently verified |
The entries above ground specific slices of this program (workplace safety for staff, published guidance, the manufacturer's own documentation). The rest of the pack is Telure's own curated practice, and is stated as such.
The manufacturer’s documentation governs
Where a manufacturer's documentation sets an inspection type or an interval for a piece of equipment, that documentation governs. The pack's cadences are a program to build on, not a replacement: when the two differ, Telure shows the difference so it can be seen and documented, and the recorded schedule follows the manufacturer.
Where Telure stands
The Telure Standard is Telure's own curated program. Telure is not affiliated with, endorsed by, or licensed by any standards body or association named here, and adopting the Telure Standard does not make a facility compliant with, approved under, or certified to any standard. Where equipment is involved, the manufacturer's documentation governs inspection types and intervals.